LPC96P Low Voltage Integrated Monitoring Device

Application Scenarios:Medium /High Voltage Cabinet,Low Voltage Wiring Cabinet

PRODUCT OVERVIEW

The device in line with the distribution network standardized design 0.4kv Los-voltage switchgear design specification requirements,large screen dot matrix display,using 96,shape and very short gauge depth,especially suitable for applications with narrow installation space,industrial standard wide temperature LCD display,with good high and low temperature display characteristics,the terminal can achieve full power measurement and display,including dynamic alarm,switching input and output status,SOE event recording,compound rate,loop load ratio display,harmonics,etc,support dual communication,transmission output function.It has the function of fault judgment such as short circuit,overload,phase loss,phase sequence,and zero break.It adopts snap-on fixed design to improve the efficiency of cabinet assembly,which is suitable for power industry switchgear distribution panel circuit distribution measurement and control.

KEY FEATURES

  • Overall monitoring
  • High level protection
  • Modular design

 

  

Signal Input

Line

Three phase 3 line, 3 phase, 4 line

Frequency

45~65Hz

Voltage

AC 57.7/100V, 230/380V

Over load:1.2 times the rated value(continuous);

1.4 times rated voltage(10s), 2, times the rated value 1s

Power consumption:< 0.5VA (each line)

Current

AC 1A, 5A

Overload: 1.2 times the rated value (continuous);

20 times the rated value /10 second.

Consumption: < 0.25VA (each line)

Accuracy

V、C、P

0.2

Active

0.5s

Reactive

2

Zero Current (residue)

20mA~1A(±1%); 1A~2A(±2.5%)

Harmonic Sampling

128point/cycle, FFT method,breakdown judging

Power Supply

Range: AC/DC 85V~265V

Consumption: main power consumption≤5VA.

Relay Output

Touch point type: normally open (level output jog mode)

Touch point capacity: AC 250V/3A  DC 30V/3A.

Power Pulse Output

Output mode: optocoupler pulse of open collector

Switch Alue Output

Support dry contact input, DC12V power supply built-in;

Resolution≤5mS

Communication

RS485 interface Modbus-RTU protocol or LT645 stipulation;

Lora, zigbee (wireless communication optional)

Security

Working Pressure

Among APS, voltage signal, current signal AC 2kV/1min;

Working frequency among switch value, pulse output, communication, AC 1kV/1min.

Insulation resistance

Input, output terminal to the chassis>100MΩ.

Electromagnetic

Compatibility

Reach IEC 61000 standard (level 4)

Level of Protection

IP51 (front), IP30 (inside)(except for terminal)

Working Life Designed

10years

Working

Environment

 

Meter Working Temperature: -25℃~+80℃;

LCD Working Temperature: -20℃~+80℃;

Storage Temperature: -40℃~+85℃;

Relative Humidity: ≤99% no condensation;

Elevation: ≤2500m.

 
 

LPC96P Low Voltage Integrated Monitoring Device

《性房纵欲》在线观看| 王祺扬| 微信公众号Ip属地怎么改| 导数复幺求| 新疆专业技术管理平台登录入口 | 成全高清免费完整观看| 李雅越过山丘 中国好声音| 海尔斯km3| 下届欧洲杯| bluc topaz| 聪惠网| 蓝猫淘气3000问之星际大战| 石器时代公益服| 女士穿紧身裸体开裆光滑皮裤| 壮丁也是兵 电视剧| 无码| 我的小后妈中字ID| 《致命审判》观看完整版高清 | 蜂火连城| 男生把女生QQ放在一起的原因 | 我与地坛读书分享| 黑狼d| 逾期无力还款最佳处理方法 | 中国传统体育项目| 灯火里的中国五线谱| 门第| 2024年税务师电子版教材pdf| ip地址仪置查询| 加强纪律建设,| 麻豆 无码 国产在线观看